Zhengzhou Xianghe Electrical Electric 
Equipment Manufacturing Co.,Ltd.

Transformer

Power distribution monitor device

pubdate:2019-5-21 14:38:17

Power distribution monitor device

Power distribution monitor device:
Dimension:
Height×width×depth:555×496×250
Technique parameter:
S N
Items
Parameter
Remark
1
Rated voltage
AC 400V
 
2
Rated signal current
AC (0~5)A
 
3
Rated frequency
50Hz
 
4
Power supply voltage
AC (85~264)V
 
5
Control output port voltage output
(12±1)V
Control motion
0V
No control motion
6
Dielectric intensity
2.5kV 1min
Between the main circuit and against earth
2.0kV 1min
Assist circuit against earth
7
Insulation level
≥5MΩ
 
8
Protection level
IP33
 
9
Average no failure operation time
>10000h
 
10
Over-loading capacity
0.8~1.2 times as the rated voltage,continuous work
11
Execute standards
GB/T 13729-2002 《Tele-motion terminal unit》
JB/T 9663-1999 《LV reactive power compensator controller》
Q/XH 004-2007 《XHPZ-400A type extensible reactive power compensating distribution monitor device》